Water Blocked P19 or P19/P21 RFOU 12/20KV
Applications
-
These cables are partially water blocked, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.
Standards
-
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004 VG 95218 part 29
Construction
-
l Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.
l Conductor Screen: Semi conducting material.
l Insulation: Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
l Insulation Screen: Semi conducting material and tinned copper wire braid.
l Filler: Water blocking fillers, if required.
l Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
l Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
l Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
l Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P19), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P19/P21), coloured red.
l Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
Optional
- P20 or P20/P22 RFOU/TFOU 18/30(36) kV.
Electrical Characteristics
-
Nominal Cross Section Area mm² 16 25 35 50 70 95 Nominal Conductor Diameter mm 5.2 6.5 7.4 8.7 10.3 12.2 Maximum DC Resistant@20℃ Ω/km 1.16 0.734 0.529 0.391 0.27 0.195 Continuous Current Rating@45℃1 Core A 96 127 157 196 242 293 Continuous Current Rating@45℃3 Core A 67 89 110 137 169 205 Short Circuit Current 1s A 2290 3580 5010 7150 10020 13590 Operating Voltage KV 12/20 12/20 12/20 12/20 12/20 12/20
-
Nominal Cross Section Area mm² 120 150 185 240 300 Nominal Conductor Diameter mm 13.8 15.1 17.0 19.6 21.9 Maximum DC Resistant@20℃ Ω/km 0.154 0.126 0.1 0.0762 0.0607 Continuous Current Rating@45℃1 Core A 339 389 444 522 601 Continuous Current Rating@45℃3 Core A 237 272 311 365 421 Short Circuit Current 1s A 17170 21460 26470 34340 42930 Operating Voltage KV 12/20 12/20 12/20 12/20 12/20
Ambient Temperature Correction Factors
-
Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80 Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Mechanical and Thermal Properties
- Bending Radius :15×OD (during installation); 9×OD (fixed installed).
- Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight
Construction No. of cores×Cross section (mm²) |
Nominal Insulation Thickness mm | Nominal Bedding Thickness mm | Nominal Inner Sheath Thickness mm | Nominal Outer Sheath Thickness mm | ||
Nominal Overall Diameter mm |
Nominal Weight kg/km |
|||||
1×16 | 5.5 | 1.4 | 1.2 | 1 | 30.0±2 | 1260 |
1×25 | 5.5 | 1.5 | 1.2 | 1.2 | 34.0±2 | 1607 |
1×35 | 5.5 | 1.8 | 1.3 | 1.2 | 34.7±2 | 1675 |
1×50 | 5.5 | 1.8 | 1.4 | 1.2 | 36.2±2 | 1885 |
1×70 | 5.5 | 1.9 | 1.4 | 1.2 | 37.0±2 | 2174 |
1×95 | 5.5 | 2 | 1.5 | 1.4 | 39.8±2 | 2594 |
1×120 | 5.5 | 2 | 1.5 | 1.4 | 41.6±2 | 2951 |
1×150 | 5.5 | 2.1 | 1.6 | 1.4 | 43.5±2 | 3407 |
1×185 | 5.5 | 2.2 | 1.6 | 1.4 | 45.7±2 | 3953 |
1×240 | 5.5 | 2.3 | 1.7 | 1.6 | 49.0±2 | 4736 |
1×300 | 5.5 | 2.4 | 1.8 | 1.6 | 51.7±2 | 5581 |
3×16 | 5.5 | 1.8 | 2 | 1 | 57.1±2 | 5198 |
3×25 | 5.5 | 1.9 | 2 | 1.2 | 64.6±2 | 5990 |
3×35 | 5.5 | 2.9 | 2.1 | 1.2 | 65.0±2 | 6290 |
3×50 | 5.5 | 3 | 2.2 | 1.2 | 67.8±2 | 7077 |
3×70 | 5.5 | 3.1 | 2.3 | 1.2 | 71.5±2 | 8180 |
3×95 | 5.5 | 3.3 | 2.4 | 1.4 | 75.8±2 | 9608 |
3×120 | 5.5 | 3.4 | 2.5 | 1.4 | 79.8±2 | 11109 |
3×150 | 5.5 | 3.6 | 2.6 | 1.4 | 84.7±2 | 12752 |
3×185 | 5.5 | 3.8 | 2.7 | 1.4 | 92.3±2 | 12878 |
3×240 | 5.5 | 4 | 2.9 | 1.6 | 99.3±2 | 15461 |
3×300 | 5.5 | 4.2 | 3 | 1.6 | 105.1±2 | 18050 |